FIELD TESTING
Evidence · PD-2041
48 Pinecrest Dr · Pinecrest Dental
Review current testCurrent test
Device
Febco 850 · DC · 1 in · PD-2041
Result
Pass
Tester / gauge
Ray Morgan / Watts TK-9A · G-8814
Site
48 Pinecrest Dr · Pinecrest Dental
Initial DC test
Check valve 1
1.8 psid
Pass · minimum 1.0 psid
Check valve 2
1.4 psid
Pass · minimum 1.0 psid
Evidence
Customer signature
Per selected verified template; no unsupported waiver
Tester signature
Ray Morgan · current saved signature
Optional current-visit photo
Device / site photo
Attach evidence for PD-2041 at 48 Pinecrest Dr