Search customers, addresses, serials…
Synced
TODAY 09/10/2026

FIELD TESTING

Evidence · BP-3018

88 Briar Park · Briar Park Center

Review current test

Current test

Device

Ames 2000SS · DCDA · 4 in · BP-3018

Result

Pass

Tester / gauge

Ray Morgan / Watts TK-9A · G-8814

Site

88 Briar Park · Briar Park Center

Mainline · DC

Check valve 1

1.9 psid

Pass · minimum 1.0 psid

Check valve 2

1.6 psid

Pass · minimum 1.0 psid

Bypass · DC

Check valve 1

1.4 psid

Pass · minimum 1.0 psid

Check valve 2

1.2 psid

Pass · minimum 1.0 psid

Evidence

Customer signature

Per selected verified template; no unsupported waiver

Tester signature

Ray Morgan · current saved signature

Optional current-visit photo

Device / site photo

Attach evidence for BP-3018 at 88 Briar Park