FIELD TESTING
Evidence · BP-3018
88 Briar Park · Briar Park Center
Review current testCurrent test
Device
Ames 2000SS · DCDA · 4 in · BP-3018
Result
Pass
Tester / gauge
Ray Morgan / Watts TK-9A · G-8814
Site
88 Briar Park · Briar Park Center
Mainline · DC
Check valve 1
1.9 psid
Pass · minimum 1.0 psid
Check valve 2
1.6 psid
Pass · minimum 1.0 psid
Bypass · DC
Check valve 1
1.4 psid
Pass · minimum 1.0 psid
Check valve 2
1.2 psid
Pass · minimum 1.0 psid
Evidence
Customer signature
Per selected verified template; no unsupported waiver
Tester signature
Ray Morgan · current saved signature
Optional current-visit photo
Device / site photo
Attach evidence for BP-3018 at 88 Briar Park