FIELD TESTING
Evidence · MC-2108
66 Maple Court · Maple Court Homes
Review current testCurrent test
Device
Watts 008PCQT · SVB · 3/4 in · MC-2108
Result
Pass
Tester / gauge
Ray Morgan / Watts TK-9A · G-8814
Site
66 Maple Court · Maple Court Homes
Initial SVB test
Air inlet opening
1.2 psid
Pass · minimum 1.0 psid
Check valve
1.5 psid
Pass · minimum 1.0 psid
Evidence
Customer signature
Per selected verified template; no unsupported waiver
Tester signature
Ray Morgan · current saved signature
Optional current-visit photo
Device / site photo
Attach evidence for MC-2108 at 66 Maple Court